ELECTRIC ACTUATOR POSITIONERS
Model SSC10-115/230V
 |
A new electronic positioner
provides accurate positioning control of electric motor actuators using an
analog input signal. Setup and calibration is greatly simplified
using microprocessor based technology. There are no dip switches to
set or trim pots to adjust. Setup is quick and easy using a menu
viewed on an LED display. No external meters are required, even for
potentiometer setup. Once the initial menu settings are chosen, the
positioner performs a self-calibration routine, applying the menu
selections to actual actuator performance. Calibration values are
then stored in permanent non-volatile memory. |
Features
 | Onboard LED display facilitates setup
and calibration. |
 | Menu selection of input/output ranges
including 4-20 ma., 1-5 VDC, 2-10 VDC and 0-10 VDC, or virtually any custom
range required. |
 | Automatic calibration; no
resistors to add; no jumpers, trim pots or dip switches to adjust.
Calibration is as simple as pressing a button. |
 | Three relay outputs; fault, full closed
and full open. (A.C. Models Only.) |
 | Current sensing (over torque
protection). Optional on A.C. Models. Standard on D.C. Models |
 | Menu selectable fail options. |
 | Intelligent positioning reduces motor
cycling, increases motor life and extends the actuator duty. |
 | Auto-jog feature. Constantly
corrects and refines the positioning accuracy. |
 | Always wires the same; no
need to determine rotation direction during installation;
rotation is selected using the menu. |
 | Robust power switching components,
designed specifically for actuator motors, virtually eliminates field
failures. |
Specifications
 | Power Requirements
Model SCC-115/230V: 115 or 230 VAC, 1 phase,
50/60 Hz. (Jumper selectable)
Model SCC-24VAC: 24 VAC, 50/60 Hz.
Model SCC-24VDC: 10-28VDC |
 | Input Command Signal
Menu selectable factory defaults: 4-20mADC, 1-5VDC,
2-10 VDC, 0-10 VDC
Infinite adjustment using menu system. |
 | Signal Impedance
Input: 250 ohm current, 200kohm voltage
Output: maximum load 500 ohm current, 500
ohm voltage |
 | Size: 3-1/2 x 1-5/8 x 4 in. |
 | Output Command Signal
Menu selectable factory defaults: 4-20 mADC, 1-5VDC, 2-10VDC, 0-10
VDC.
Infinite adjustment using menu system |
 | Power Output
Solid state, isolated from the input command and output position signals and
rated at:
- 5 amps continuous at 115 VAC, 230 VAC, 24 VAC
-10 amps continuous at 25 VDC
All ratings assume the positioner is mounted on the actuator base plate. |
 | Sensitivity
Fully adjustable from 0.5% of total span, factory set to 1% of total span. |
 | Dead Band
Automatically set during calibration. Factory default at 1% of total
span. Additional settings available using the menu system. |
 | Zero Adjustment
Automatically set during calibration |
 | Span Adjustment
Automatically set during calibration. |
 | Split Range
Settable within the span range using at least 1.5VDC or 3mA of input. |
 | Ambient Temperature |
 | - 40 degrees F (with heater) to + 150
degrees F (-40C to +65C) |
 | Action or Loss of Command Signal
Factory default: fail in last position (no movement)
Additional settings available through menu:
- Fail open (maximum signal value)
- Fail closed (minimum signal value)
- Fail to a preset position |
 | Relay Outputs - A.C. Models Only
Three dry contacts outputs:
- Fault indicating loss of power, fuse failed,
command signal loss or failure to move
to
position in preset time.
- End of travel open
- End of travel closed
- Contact Ratings: 1A @ 30VDC, 0.5A @ 135VAC
resistive |